Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
93
Configuring the terminal block
5
Before you configure the inputs and outputs of the inverter, you should have completed the
basic commissioning, see Chapter Commissioning (Page 55) .
The assignment of the inputs and outputs in the factory setting and after the basic
commissioning are listed in Chapter Wiring examples for the factory settings (Page 64).
5.1
Digital inputs
The digital inputs are pre-assigned specific functions in the factory. Depending on the
Control Unit version, up to 8 digital inputs are available, of which, digital inputs DI 11 and
DI 12 (terminals 3 and 10) can also be used as analog inputs.
Table 5- 1
Pre-assignment of the digital inputs
Pre-assignment after basic commissioning
Terminal Input
Control via terminal strip
Control via fieldbus
Changing the pre-
assignment via
5
DI 0
Switch motor on and off
(ON/OFF1) (p0701 = 1)
No pre-assignment
(p0701 = 0)
p0701
6
DI 1
Reverse direction of
motor rotation (p0702 =
12)
No pre-assignment
(p0702 = 0)
p0702
7
DI 2
Acknowledge faults (p0703 = 9)
p0703
8
DI 3
Fixed speed setpoint selection bit 0 (p0704 = 15)
p0704
16
DI 4
Fixed speed setpoint selection bit 1 (p0705 = 16)
Not available with Control Units CU240B-2 and
CU240B-2 DP
p0705
17
DI 5
Fixed speed setpoint selection bit 2 (p0705 = 17)
Not available with Control Units CU240B-2 and
CU240B-2 DP
p0706