Commissioning
4.5 Commissioning with STARTER
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
79
● If you have installed the PC COM-Port (USS) interface, close the dialog box and now call
up "Properties - PC COM-Port (USS)".
● In this dialog box, select the COM address that you defined when setting the USB
interface. Select 115200 as baud rate.
● You can check the correctness of the settings using the "Read" button in the "Baud rate
test" field. If your interface has been correctly set, then you see the baud rate that has
been determined:
● If the PC cannot establish a connection to the converter, then "???" appears in the baud
rate display field.
In this case, check the number of the COM interface and the connecting cable.
● Under the "RS 485" tab, in addition, select the "Automatic mode".
● When you click "OK", the "Set PG/PC Interface" dialog box is displayed again.
● When you choose "OK" again, this takes you back to the Project Wizard.