Technical data
10.3 Technical data, Power Modules
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
265
10.3.1
Technical data, PM240
Note
The given input currents are valid for operation without a line reactor for a line voltage of 400
V with Vk = 1 % referred to the rated power of the inverter. If a line reactor is used, the
specified values are reduced by a few percent.
General data, PM240 - IP20
Feature
Version
Line voltage
3-ph. 380 V … 480 V AC ± 10 %
The actual permissible line voltage depends on the installation altitude.
Input frequency
47 Hz … 63 Hz
Power factor λ
0,7 ... 0,85
Starting current
Less than the input current
Pulse frequency (factory
setting)
4 kHz for 0.37 kW ... 90 kW
2 kHz for 110 kW ... 250 kW
The pulse frequency can be increased in 2 kHz steps. A higher pulse frequency reduces
the permissible output current.
Electromagnetic compatibility
The devices are suitable for environmental classes C1 and C2 in conformance with
IEC61800-3. For details, see the Hardware Installation Manual, Appendix A2
Braking methods
DC braking, compound braking, dynamic braking with integrated braking chopper
Degree of protection
IP20
Operating temperature
● without power reduction
● with power reduction
LO operation of all power
ratings
HO operation:
0.37 kW ... 110 kW
HO operation: 132 kW … 200
kW
all power ratings, HO/LO
0 °C … +40 °C (32 °F … 104 °F)
0 °C … +50 °C (32 °F … 122 °F)
0 °C … +40 °C (32 °F … 104 °F)
up to 60 °C (140° F), for details, refer to the Hardware
Installation Manual
Storage temperature
-40 °C … +70 °C (-40 °F … 158 °F)
Relative humidity
< 95 % RH - condensation not permissible
Environmental requirements
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging
chemical substances
Shock and vibration
Do not allow the inverter to fall and avoid it being subject to hard shocks. Do not install
the inverter in an area where it could be continuously subject to vibration.
Electromagnetic radiation
Do not install the inverter close to sources of electromagnetic radiation.
Installation altitude
● without power reduction
● with power reduction
0.37 kW ... 132 kW
160 kW ... 250 kW
all power ratings
up to 1000 m (3300 ft) above sea level
up to 2000 m (6500 ft) above sea level
up to 4000 m (13000 ft) above sea level, for details refer to the
Hardware Installation Manual.
Standards
UL, cUL, CE, C-tick, SEMI F47
In order that the system is UL-compliant, UL-certified fuses, overload circuit-breakers or
intrinsically safe motor protection devices must be used.