Functions
7.6 Motor control
Inverter with CU240B-2 and CU240E-2 Control Units
170
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
7.6.1.1
V/f control with linear characteristic
V/f control with a linear characteristic is
mainly used in applications in which the
motor torque must be independent of the
motor speed. Examples of such
applications include horizontal conveyors
or compressors.
)UHTXHQF\
5DWHGIUHTXHQF\
9ROWDJH
5DWHGYROWDJH
I
8
V/f control with a parabolic characteristic
is used in applications in which the motor
torque increases with the motor speed.
Examples of such applications include
pumps and fans.
V/f control with square-law characteristic
reduces the losses in the motor and
inverter due to lower currents than when
a linear characteristic is used.
)UHTXHQF\
5DWHGIUHTXHQF\
9ROWDJH
5DWHGYROWDJH
8
I
Parameters Description
P1300
Open-loop/closed-loop control operating mode
0: V/f control with linear characteristic
2: V/f control with parabolic characteristic
Note
V/f control with a square-law characteristic must not be used in applications in which a high
torque is required at low speeds.