Adapting the terminal strip
5.3 Digital outputs
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
88
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
5.3
Digital outputs
Digital output terminals
Changing the function of the digital output
'21&
'212
'2&20
'212
'2&20
BO: ryyxx.n
p0731
p0730
'21&
'212
'2&20
p0732
Interconnect the digital output with a binector output of your
choice.
Binector outputs are designated with "BO" in the parameter
list of the List Manual.
Table 5- 3
Binector outputs of the inverter (selection)
0
Deactivating digital output
r0052.9
Process data control
r0052.0
Drive ready
r0052.10
f_actual >= p1082 (f_max)
r0052.1
Drive ready for operation
r0052.11
Alarm: Motor current/torque limit
r0052.2
Drive running
r0052.12
Brake active
r0052.3
Drive fault active
r0052.13
Motor overload
r0052.4
OFF2 active
r0052.14
Motor CW rotation
r0052.5
OFF3 active
r0052.15
Inverter overload
r0052.6
Closing lockout active
r0053.0
DC braking active
r0052.7
Drive alarm active
r0053.2
f_actual > p1080 (f_min)
r0052.8
Setpoint/actual value discrepancy
r0053.6
f_actual ≥ setpoint (f_setpoint)
A complete list of the binector outputs is provided in the List Manual.
Table 5- 4
Example:
'2
r0052.3
52.3
p0731
Signal fault via digital output 1.
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, see the parameter list and the function block diagrams 2230 ff of the
List Manual.