Description
2.4 Reactors and filters
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
26
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
PM230 Power Module, IP55 degree of protection / UL Type 12
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
PM230, 3AC 400V - power units with low line reactions
Power range (LO) in kW
0,37 … 3
4 … 7,5
11 … 18.5
22 … 30
37 … 45
55 … 90
line filter, Class A
●
●
●
●
●
●
line filter, class B
●
●
●
●
●
●
2.4
Reactors and filters
Depending on the Power Module, the following combinations with filters and reactors are
permitted:
Line-side components
Load-side components
Power Module
Line reactor
Line filters
class B
Braking
resistor
Sine-wave filter Output reactor
PM230
-
-
-
-
-
PM240
●
●
●
●
●
PM250
-
●
-
●
●
For further details, refer to the connection example in section Procedure for installing the
frequency inverter (Page 27).