Load failure monitoring via digital input
Using this function, the inverter monitors the load failure of the driven machine, e.g. for fans
or conveyor belts.
WRVLJQDOHYDOXDWLRQ
S
U[
39
',[
Figure 7-19 Load failure monitoring by means of a digital input
Table 7- 44 Setting load failure monitoring
Parameter
Description
p2193 = 1 … 3 Load monitoring configuration (factory setting: 1)
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
p2192
Load monitoring delay time (factory setting 10 s)
If, after the motor is switched on, the "LOW" signal is present on the associated
digital input for longer than this time, a load failure is assumed (F07936)
p3232 = 722.x Load monitoring failure detection (factory setting: 1)
Interconnect the load monitoring with a digital input of your choice.
For more information, see the List Manual (the parameter list and function diagram 8013).