Function description
Procedure
1. Insert the memory card into the converter.
2. Switch on the power supply for the converter.
3. The converter loads the settings from the memory card.
4. After loading, check whether the converter outputs Alarm A01028.
– Alarm A01028:
The loaded settings are not compatible with the converter.
Set p0971 = 1 to delete the alarm. Check the converter settings. We recommend that you
recommission the drive.
– No alarm A01028:
Perform a reduced acceptance test.
Reduced acceptance test after component replacement and firmware change
(Page 387)
You have transferred the settings to the converter.
❒
10.2.2.2
Download from IOP-2 operator panel
Overview
You can transfer the converter settings that are backed up on the IOP-2 operator panel back into
the converter.
Requirement
The following preconditions apply:
• You know the password for the converter safety functions.
• The converter power supply has been switched on.
• The converter settings are not protected against copying.
Download with active know-how protection with copy protection (Page 375)
Corrective maintenance
10.2 Downloading the converter settings
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
371