9.4
Identification & maintenance data (I&M)
I&M data
The converter supports the following identification and maintenance (I&M) data.
I&M data Format
Explanation
Associated param‐
eters
Example for the
content
I&M0
u8[64] PROFIBUS
u8[54] PROFINET
Converter-specific data, read only
-
See below
I&M1
Visible String [32]
Plant/system identifier
p8806[0 … 31]
"ak12-ne.bo2=fu1"
Visible String [22]
Location code
p8806[32 … 53]
"sc2+or45"
I&M2
Visible String [16]
Date
p8807[0 … 15]
"2013-01-21 16:15"
I&M3
Visible String [54]
Any comment
p8808[0 … 53]
-
I&M4
Octet String[54]
Check signature to track changes for Safe‐
ty Integrated.
This value can be changed by the user.
The test signature is reset to the value
generated by the machine if p8805 = 0 is
used.
p8809[0 … 53]
Values of r9781[0]
and r9782[0]
When requested, the converter transfers its I&M data to a higher-level control or to a PC/PG with
installed STEP 7 or TIA Portal.
I&M0
Designation
Format
Example for the con‐
tent
Valid for PROFI‐
NET
Valid for PROFI‐
BUS
Manufacturer-specific
u8[10]
00 … 00 hex
---
✓
MANUFACTURER_ID
u16
42d hex (=Siemens)
✓
✓
ORDER_ID
Visible String [20]
"6SL3246-0BA22-1FA0"
✓
✓
SERIAL_NUMBER
Visible String [16]
"T-R32015957"
✓
✓
HARDWARE_REVISION
u16
0001 hex
✓
✓
SOFTWARE_REVISION
char, u8[3]
"V" 04.70.19
✓
✓
REVISION_COUNTER
u16
0000 hex
✓
✓
PROFILE_ID
u16
3A00 hex
✓
✓
PROFILE_SPECIFIC_TYPE
u16
0000 hex
✓
✓
IM_VERSION
u8[2]
01.02
✓
✓
IM_SUPPORTED
bit[16]
001E hex
✓
✓
Alarms, faults and system messages
9.4 Identification & maintenance data (I&M)
Distributed converter for SIMOGEAR geared motors
350
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL