Selecting the number of drive data sets
The number of drive data sets (1 ... 4) is defined by parameter p0180.
Parameter
Description
p0010 = 0
Drive commissioning: Ready
p0010 = 15
Drive commissioning: Data sets
p0180
Number of Drive Data Sets (DDS)
Copying the drive data sets
Parameter
Description
p0819[0]
Source drive data set
p0819[1]
Target drive data set
p0819[2] = 1
Starts the copy operation
Parameter
Parameter
Description
Factory setting
p0010
Drive commissioning parameter filter
1
r0051
CO/BO: Drive data set DDS effective
-
p0180
Number of Drive Data Sets (DDS)
1
p0819[0 … 2]
Copy drive data set DDS
0
p0820[C]
BI: Drive data set DDS selection, bit 0
0
p0821[C]
BI: Drive data set DDS selection, bit 1
0
p0826[M]
Motor changeover, motor number
0
Further information
The converter switches the motor data set (MDS) and the power unit data set (PDS) together
with the drive data set (DDS).
Advanced commissioning
8.30 Switchover between different settings
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
343