Motor protection by calculating the temperature
Overview
The converter calculates the motor temperature based on a thermal motor model. After
commissioning, the converter sets the thermal motor type to match the motor.
The thermal motor model responds far faster to temperature increases than a temperature
sensor.
If the thermal motor model is used together with a temperature sensor, e.g. a Pt1000, then the
converter corrects the model according to the measured temperature.
Function description
Thermal motor model 2 for induction motors
The thermal motor model 2 for induction motors is a thermal 3-mass model, consisting of stator
core, stator winding and rotor. Thermal motor model 2 calculates the temperatures - both in the
rotor as well as in the stator winding.
ุ
W
˽
˽U
S
S
S
S
S!
S
$
)
U
L
U
Figure 8-72
Thermal motor model 2 for induction motors
Parameter
Table 8-73
Thermal motor model 2 for induction motors
Number
Name
Factory setting
r0034
CO: Thermal motor load
- %
r0068[0 … 1]
CO: Absolute actual current value
- Arms
p0344[M]
Motor weight (for thermal motor model)
0 kg
p0604[M]
Mot_temp_mod 2/KTY alarm threshold
130 °C
p0605[M]
Mot_temp_mod 1/2/sensor threshold and temperature value 145 °C
p0610[M]
Motor overtemperature response
12
p0612[M]
Mot_temp_mod activation
0000 0010 0000
0010 bin
p0625[M]
Motor ambient temperature during commissioning
20 °C
p0627[M]
Motor overtemperature, stator winding
80 K
r0632[M]
Mot_temp_mod stator winding temperature
- °C
p0640[D]
Current limit
0 Arms