DC braking initiated by a control command
'&EUDNLQJDFWLYH
'&EUDNLQJDFWLYDWLRQ
'HPDJQHWL]LQJWKH
PRWRU
Q
S
U
S
W
W
W
Figure 8-65
Activating DC braking via a control command
Set p1231 = 4 and p1230 = control command.
The control command "DC braking activation" activates and deactivates the DC braking:
• 1 signal:
The converter de-energizes the motor for the motor de-excitation time p0347 in order to
demagnetize the motor.
The converter activates the DC braking.
• 0 signal: The drive switches back to normal operation.
DC braking when falling below a starting speed
'&EUDNLQJDFWLYH
'&EUDNLQJDFWLYDWLRQ
'HPDJQHWL]LQJWKH
PRWRU
6SHHGDWWKHVWDUWRI'&
EUDNLQJ
'&EUDNLQJGXUDWLRQ
Q
S
U
S
W
W
W
S
S
Figure 8-66
DC braking when falling below a starting speed
Set p1231 = 14 and p1230 = control command.
Advanced commissioning
8.20 Electrically braking the motor
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
313