8.17.2
Invert setpoint
Function description
S
[
\
[
\
W
\
\
[
[
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal
of your choice.
Table 8-54
Application examples showing how a setpoint is inverted
Parameter
Description
p1113 = 722.1
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
p1113 = 2090.11
Inverts the setpoint via the fieldbus (control word 1, bit 11).
Parameter
Number
Name
Factory setting
p1113[C]
BI: Setpoint inversion
Dependent on the
converter
Advanced commissioning
8.17 Setpoint calculation
Distributed converter for SIMOGEAR geared motors
270
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL