8.16.4
Electromechanical potentiometer
The converter has an electromechanical potentiometer.
The potentiometer is hardwired with the internal analog input 2.
When using USS or Modbus communications, the potentiometer provides
by default the main setpoint.
$QDORJLQSXW
DFWXDOYDOXH
0DLQVHWSRLQW
6XSSOHPHQWDU\VHWSRLQW
S
S
r0755[2]
Figure 8-40
Potentiometer as setpoint source
Table 8-47
Setting the potentiometer as setpoint source
Parameter
Remark
p1070 = 755[2]
Main setpoint
Interconnect the main setpoint with the internal analog input 2
p1075 = 755[2]
Additional setpoint
Interconnect the additional setpoint with the internal analog input 2.
Advanced commissioning
8.16 Setpoints
Distributed converter for SIMOGEAR geared motors
262
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL