
8.15.2.8
Complete commissioning
Overview
You must exit commissioning the safety functions and save the settings.
Requirement
You are online with Startdrive.
Function description
Procedure
1. Press the "End safety commissioning" button.
2. Confirm the prompt for saving your settings (copy RAM to ROM).
3. Disconnect the online connection.
4. Select the "Load from device (software)" button.
5. Save the project.
6. Switch off the converter power supply.
7. Wait until all LEDs on the converter go dark (no voltage condition).
8. Switch on the converter power supply again.
Your settings are now active.
❒
Advanced commissioning
8.15 Safe Torque Off (STO) safety function
Distributed converter for SIMOGEAR geared motors
254
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL