PNU (parameter number) and page index
Parameter number
PNU
Page index
0000 … 1999
0000 … 1999
0 hex
2000 … 3999
0000 … 1999
80 hex
6000 … 7999
0000 … 1999
90 hex
8000 … 9999
0000 … 1999
20 hex
10000 … 11999
0000 … 1999
A0 hex
20000 … 21999
0000 … 1999
50 hex
29000 … 29999
0000 … 1999
70 hex
30000 … 31999
0000 … 1999
F0 hex
60000 … 61999
0000 … 1999
74 hex
Subindex
For indexed parameters, the parameter index is located in subindex as hexadecimal value.
PWE: Parameter value or connector
Parameter values or connectors can be located in the PWE.
Table 8-31
Parameter value or connector
PWE 1
PWE 2
Parameter value
Bit 15 … 0
Bit 15 … 8
Bit 7 … 0
0
0
8-bit value
0
16-bit value
32-bit value
Connector
Bit 15 … 0
Bit 15 … 10
Bit 9 … 0
Number of the connector
3F hex
The index or bit field
number of the connec‐
tor
Examples
Read request: Read out serial number of the Power Module (p7841[2])
To obtain the value of the indexed parameter p7841, you must fill the telegram of the parameter
channel with the following data:
• PKE, Bit 12 … 15 (AK): = 6 (request parameter value (field))
• PKE, Bit 0 … 10 (PNU): = 1841 (parameter number without offset)
Parameter number = PNU + offset (page index)
(7841 = 1841 + 6000)
• IND, bit 8 … 15 (subindex): = 2 (index of parameter)