8.5.4
Three-wire control, enable/clockwise/counterclockwise rotation
Function description
&ORFNZLVH
&RXQWHUFORFNZLVH
21
&RXQWHUFORFNZLVH
21
&ORFNZLVH
(QDEOH2))
6SHHGVHWSRLQW
W
W
W
W
6723
6723
6723
Figure 8-8
Three-wire control, enable/clockwise/counterclockwise rotation
The "Enable" command is a precondition for switching on the motor. Commands "ON clockwise
rotation" and "ON counter-clockwise rotation" switch on the motor - and simultaneously select
a direction of rotation. Removing the enable switches the motor off (OFF1).
Table 8-17
Function table
Enable / OFF1
ON clockwise rota‐
tion
ON counter-clock‐
wise rotation
Function
0
0 or 1
0 or 1
The motor stops.
1
0→1
0
Clockwise motor rotation.
1
0
0→1
Counter-clockwise motor rotation.
1
1
1
The motor stops.
Examples
Table 8-18
Three-wire control and setting the assignment of the digital inputs
Parameter
Description
p3334 = 3
2/3 wire control selection
3: Three-wire control enable/clockwise/counterclockwise rotation
p3330[C] = 722.0
BI: 2/3 wire control command 1 (enable/OFF1)
Command is received via digital input 0
p3331[C] = 722.1
BI: 2/3 wire control command 2 (ON clockwise rotation)
Command is received via digital input 0
p3332[C] = 722.2
BI: 2/3 wire control command 3 (ON counter-clockwise rotation)
Command is received via digital input 0
Advanced commissioning
8.5 Controlling clockwise and counter-clockwise rotation via digital inputs
Distributed converter for SIMOGEAR geared motors
178