8.4.4
Analog inputs
Function description
;
2
8
4
5
6
1
7
3
U>@
&,S\\\\
S>@
U>@
&,S\\\\
S>@
$,
$,
0
Defining the analog input type
Each analog input can be used as a current or voltage input.
To define the type of analog input, you need to set both the p0756 parameter and the
corresponding DIP switch on the Control Unit.
The settings of p0756 and the DIP switch need to match.
NOTICE
Analog input overload
With a voltage input, the maximum voltage between analog input and ground is 35 V.
With a current input, the maximum voltage between analog input and ground is 10 V. The
maximum current is 80 mA.
Higher values overload the analog input and can damage the converter.
• Observe the maximum values when connecting the analog input.
Set the type of the analog input with the DIP switch on the converter:
&200,66,21,1*',36:,7&+
(0
%5$.(
+=
7(03(5$785(
6(1625
02725
5(9(56(
&XUUHQW
9ROWDJH
$,
9,
$,
9,
Further information on commissioning using the DIP switch:
Quick Commissioning with DIP switches (Page 108)
Table 8-5
Factory setting
Analog input
Value range
Parameter
AI0
Unipolar voltage input
0 V ... +10 V
p0756 [0] = 0
AI1
Unipolar voltage input
0 V ... + 10 V
p0756 [1] = 0
Advanced commissioning
8.4 Adapt the default setting of the inputs and outputs
Distributed converter for SIMOGEAR geared motors
166
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL