
Example
;
722.2
p0840
U
',
To switch on the motor using digital input DI 2, you must connect the status parameter of DI 2
with p0840: Set p0840 = 722.2
Parameter
Table 8-3
Binector inputs (BI) of the converter (selection)
BI
Meaning
BI
Meaning
p0810 Command data set selection CDS bit 0
p1036 Motorized potentiometer setpoint lower
p0840 ON/OFF1
p1055 Jogging bit 0
p0844 OFF2
p1056 Jogging bit 1
p0848 OFF3
p1113 Setpoint inversion
p0852 Enable operation
p1201 Flying restart enable signal source
p0855 Unconditionally open holding brake
p2103 1. Acknowledge faults
p0856 Enable speed controller
p2106 External fault 1
p0858 Unconditionally close holding brake
p2112 External alarm 1
p1020 Fixed speed setpoint selection, bit 0
p2200 Technology controller enable
p1021 Fixed speed setpoint selection, bit 1
p3330 2-3-WIRE control command 1
p1022 Fixed speed setpoint selection, bit 2
p3331 2-3-WIRE control command 2
p1023 Fixed speed setpoint selection, bit 3
p3332 2-3-WIRE control command 3
p1035 Motorized potentiometer setpoint higher
A complete list of the binector inputs is provided in the List Manual.
Further information
You can debounce the digital input signal using parameter p0724.
Additional information is provided in the parameter list and function diagrams 2210 ff.
Manuals and technical support (Page 415)
8.4.2
Analog inputs as digital inputs
Function description
;
2
8
4
5
6
1
7
3
9
0
',
',
r0722.11
r0722.12
BI: pxxxx
Advanced commissioning
8.4 Adapt the default setting of the inputs and outputs
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
163