6.2.3
Message for a memory card that is not inserted
Function description
The converter identifies that a memory card is not inserted, and signals this state. The message
is deactivated in the converter factory setting.
Activate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 2
Message A01101 for a memory card that is not inserted is activated.
❒
To cyclically signal to the higher-level control that a memory card is not inserted, connect
parameter r9401 to the send data of the fieldbus interface.
Deactivate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, … 19
2. Set p2119[x] = 3
Message A01101 for a memory card that is not inserted is deactivated.
❒
Parameter
Parameter
Explanation
Factory setting
p2118[0…19]
Change message type, message number
0
p2119[0 … 19]
Change message type, type
0
r9401
Safely remove memory card status
-
6.2.4
Manual upload with Startdrive
Overview
If you insert the memory card into a converter that is already supplied with power, you must start
the upload manually using a commissioning tool.
Uploading the converter settings
6.2 Uploading to the memory card
Distributed converter for SIMOGEAR geared motors
140
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL