Commissioning
5.9 Backup data and storage
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
89
Note
Time it takes to save the data
It can take several minutes to transfer data to the SD memory card.
Transferring the parameters from the SD memory card into the frequency inverter (download)
Parameter
Description
P0003 = 3
3: Access level 3
P0010 = 30 30: Parameter transfer
P0803 = 2
2: Start data transfer from the SD card to the EEPROM in the CU. "RDY" LED flashes.
•
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
LED lights up.
•
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.