Function diagrams
Faults and alarms
2-482
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-96 8075 – Fault/alarm configuration
- 8075 -
Function diagram
8
7
6
5
4
3
2
1
fp_S01_8075_en.vsd
DO: VECTOR, TM31, CU
SINAMICS G
17.12.04
V02.02.00
Faults and alarms - fault/alarm configuration
0. Fault code
1. Fault code
19. Fault cod
e
[0]
[1]
[19]
Changing the fault response for a maximum of 20 faults <1>
Fault response
Fault response
Fault response
[0]
[1]
[19]
0 = NONE
1 = OFF1
2 = OFF2
3 = OFF3
0. Fault code
1. Fault code
19. Fault cod
e
[0]
[1]
[19]
Changes the acknowledge mode for max. 20 faults <1>
Acknowledge mode
Acknowledge mode
Acknowledge mode
[0]
[1]
[19]
1 = Can be acknowledged after POWER ON (the electronics power supply is switched-in) if the cause of the fault has been removed
.
2 = Can be acknowledged at any time if the cause of the fault has been removed.
<1>
In the factory setting, fault responds, acknowledge mode and message type are practically and sensibly pre-assigned for all fau
lts and alarms.
Possible changes can only be made in an individual value range that is specified by SIEMENS.
When the message type is changed, the supplementary information "moves" from fault value r0949 to alarm value r2124 and vice ve
rsa.
0. Fault/alarm code
1. Fault/alarm code
19. Fault/alarm cod
e
[0]
[1]
[19]
Changes the message type - fault <==> alarm for a maximum of 20 faults/alarms <1>
Fault/alarm type
Fault/alarm type
Fault/alarm type
[0]
[1]
[19]
1 = Fault
2 = Alarm
p2100
p2101
p2118
p2119
p2126
p2127
4 = STOP1
5 = STOP2
6 = DCBRK
Background
Refer to [1020.7]