Function diagrams
Technology controller
2-470
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-86 7954 – Motorized potentiometer (r0108.16 = 1)
- 7954 -
Function diagram
8
7
6
5
4
3
2
1
fp_S01_7954_en.vsd
DO: VECTOR
SINAMICS G
17.12.04
V02.02.00
Technology controller - motorized potentiometer (r0108.16 = 1)
Tec_ctrl Mop config
0000...0111
p2230[D] (0110)
<1>
For p2230.0 = 0, this setpoint is entered after ON.
<2>
If the initial rounding-off is active (p2230.2 = 1), the selected ramp-up and ramp-down times are appropriately exceeded.
<101>
Pre-assignment of the sampling times in p0115, refer to p011
2
.
<1>
0
The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
0
Without initial rounding-of
f.
1
With initial rounding-off. The ramp-up/down time set is exceeded accordingly.
1
The setpoint for the motorized potentiometer is saved and after ON is entered using p2231.
4000.00 µs
<101>
Refer to [1020.7]
r2250
Tec_ctrl mop after RFG
Tec_ctrl mop t_up
0.0...1 000.0
s
p2247[D] (10.0)
Tec_ctrl mop t_down
0.0...1 000.0
s
p2248[D] (10.0)
<2>
<2>
Tec_ctrl mop start
-200.00...200.00 %
p2240[D] (0.00)
r2245
Tec_ctrl mop before RFG
xy
y
p2237
p2238
x
y = 0
0 0
0 1
1 0
1 1
Tec_ctrl mop min
-200.00...200.00 [%]
p2238[D] (-100.00)
Tec_ctrl mop max
-200.00...200.00 [%]
p2237[D] (100.00)
(0)
Tec_ctrl mop raise
p2235[C]
(0)
Tec_ctrl mop lower
p2236[C]
Data save active
Initial rounding-off active
1 = OFF1, enable missing
r0046.0
Old value is kept
[2614.6]