Sequence control
Function diagrams
2-423
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-44 2610 – Control unit
S4: Operation
ZSWA.00/01/02 = 1
ZSWA.11 = 1
ZSWA.06 = 0
- Pulses enabled
- Controller enabled
- If not jog operation
Setpoint enabled
- 2610 -
8
7
6
5
4
3
2
1
fp_S01_2610_en.vsd
DO: VECTOR
SINAMICS G
17.12.04
V02.02.00
Sequence control - control unit
POWER ON
S1: Power-on inhibit
ZSWA.06 = 1, ZSWA.11 =
0
ZSWA.00/01/02 = 0
Pulses inhibited
S2: Ready to power-on
ZSWA.00 = 1, ZSWA.11 =
0
- Main contactor de-energized (open)
- Wait for power-on or jogging
<2>
S5a: Ramp stop
ZSWA.00/01 = 1
ZSWA.11 =
1
ZSWA.02/06 = 0
Ramp-down to n = 0, then
inhibit the pulses
S5b: Fast stop
ZSWA.00/01 = 1, ZSWA.11 = 1
ZSWA.02/06 = 0
Bring the drive to n = 0 along the
fast stopping ramp or torque limit,
then inhibit the pulses
S3: Ready
ZSWA.00/01 = 1, ZSWA.11 = 0
ZSWA.02/06 = 0
Close line contactor
Wait for pre-charging
"0 = OFF"
&
"Enable operation"
(STWA.03)
From the line module
"Enable operation" (STWA.0
3
)
"0 = Coast dow
n
"
(STWA.01)
"0 = Fast stop"
(STWA.02)
&
"0 = OFF"
Jog 1
Jog 1
&
&
&
Pulse enable
HW[2701.8][2711.8]
"0 = Fast stop"
(STWA.02)
"0 = Coast dow
n
"
(STWA.01)
&
Pulse enable HW
[2701.8] [2711.8]
Line contacto
r
CLOSE
r0863.1
"0 = Coast dow
n
"
(STWA.01)
<1> POWER ON = 24 V electronics power supply OFF --> ON or RESET butto
n
.
<2> The control unit is implemented according to the PROFIdrive profil
e
.
p0857... p0862
2000.00 µs
Missing enable
signals
[2614]
Faults F07802...F07300
F6000
&
Pulse enable
HW[2701.8]
Drive at
standstill
Fault
with OFF1 - or
OFF3
response
Drive at
standstill
≥
1
0 V at EP terminals,
motor module
≥
1
Drive at
standstill
<4>
<4>
<4>
<4>
<4>
<4>
<4>
<4>
<4>
<4> These control commands can also be triggered by a fault response.
&
&
"Ready" from motor module
De-magnetization completed
(r0046.27 = 0)
0 V at EP terminals,
motor module
Infeed ready
p0864
&
"Commissioning completed" (p0010 = 0 and p0009 = 0)
From all states
. . .
≥
1
0 V at EP terminals,
motor module
≥
1
"0 = OFF" (STWA.00)
"0 = Coast down" (STWA.01)
"0 = Fast stop" (STWA.02)
24 V at EP terminals, motor module [2614] r0046
.8
"0 = Coast down" (STWA.01)
"0 = Fast stop" (STWA.02)
0 V at EP terminals, motor module
<5> STWA.xx = control word, sequence control, bit xx (r0898) [2501]; ZSWA.xx = status word, sequence control bit xx (r0899) [25
03].
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<1>
<5>
<5>
<5>
<5>
<5>
<5>
<4>
<5>
S5c: Jog down ramp
- Drive is ramped-down (via
the ramp-function generator)
to |n| < min_jog = 0 - then
delay time 0.0 ... 60.0 s
Jog 2
Jog mode
n_min_jog
Shutdown speed
for jogging
≥
1
Jog 2
No jogging operation
t_delay_jog
delay time
for power-down
after jogging
Jog 1 Jog 2
≥
1
"0 = OFF" Jog 1 Jog 2
OFF3
(has priority over jogging)
Drive at
standstill
OFF2 (has priority over jogging)
Function diagram