6.2.2
Testing fail-safe digital inputs
Testing sensors and fail-safe digital inputs
The inverter tests its fail-safe digital inputs and the connected sensors with a signal change at
the inputs. We recommend that you test the fail-safe digital inputs together with the forced
checking procedure (test stop).
Procedure
To test the fail-safe digital inputs, proceed as follows:
1. Actuate the relevant sensor.
2. Check the following:
– The expected safety function is active.
– The inverter signals a fault.
You have tested the fail-safe digital inputs.
Inverter signals
Parameter
Included in the PROFI‐
safe telegram
Can be interconnec‐
ted with
F-DI
F-DO
Internal event
r9722.7
✓
---
✓
STO active (basic functions)
r9773.1
✓
---
✓
STO active (extended functions)
r9722.0
✓
---
✓
SS1 active (basic functions)
r9773.6
✓
---
✓
SS1 active (extended functions)
r9722.1
✓
---
✓
SLS active
r9722.4
✓
---
✓
SDI+ active
r9722.12
✓
---
✓
SDI- active
r9722.13
✓
---
✓
Operation
6.2 Regularly testing the safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD