9. Remove the CF card and insert it into the slot on the D4x5‑2.
10.Switch the D4x5‑2 on. The D4x5‑2 powers up with the downloaded project.
Note
The components' firmware is upgraded or downgraded automatically based on the FW
version on the CF card and the FW version on the SINAMICS components (DRIVE‑CLiQ
components, CBE30-2, TB30, Power Modules, etc.).
The update can take several minutes and its progress is tracked by corresponding
messages appearing in the alarm window of SIMOTION SCOUT.
A firmware update on DRIVE-CLiQ components is indicated by the RDY LED flashing red/
green:
● FW update running: RDY LED flashes slowly (0.5 Hz)
● FW update complete: RDY LED flashes quickly (2 Hz), POWER ON required
These flashing patterns are displayed additionally via a yellow RDY LED on the
SIMOTION D/CX32‑2, indicating that components connected to SIMOTION D/CX32‑2 are
carrying out a firmware update or that all components have finished their firmware update.
Components that require a POWER ON after the firmware update will indicate this through
a rapidly flashing RDY-LED. Go offline with SCOUT and switch the 24 V supply off/on
(POWER ON) at the respective components for initialization.
CBE30-2 option board:
During the firmware update, the OPT LED of the SIMOTION D module and the SYNC LED
of the CBE30-2 flash green.
7.2.6
Loading a project, including sources and additional data
Overview
It is possible to download additional data (e.g. sources) to the target device when saving a
project to the CF card or downloading to the D4x5‑2.
These data are required for:
● Online object comparison (e.g. additional properties)
● Various detailed comparisons (e.g. ST source file comparison)
● Synchronization with online objects
In order to be able to load a project's sources and additional data to the PG, this must be
specified in the project under "Options" > "Settings" > "Download" > "Store additional data on
the target device". Alternatively, this setting can also be made when the data is loaded to the
target device/target system.
If the sources and additional data have been saved on the CF card, the option described in
the sections that follow becomes available.
Commissioning (software)
7.2 Performing the configuration for the D4x5-2 offline
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
201