Application planning
4.4 Mounting positions and fastening
SIMOTION P320-3 and Panel Fronts
74
Manual, 02/2012
4.4.2
Type of fixation
The control unit is secured in the mounting cut-out either with clamps or screws.
NOTICE
Securing with screws is not possible with the 12" touch screen variant.
Select the mounting type suitable for your requirements for the degree of protection.
4.4.3
Degree of protection
Principles
The degree of protection provided by the front side can only be guaranteed when the
mounting seal lies completely against the mounting cutout.
CAUTION
Please ensure that the material strength at the mounting cutout does not exceed 6 mm.
Please follow the specifications for the dimensions, seePanel front dimensions (Page 122)
and SIMOTION panel fronts installation dimensions (Page 123).
The degrees of protection are only guaranteed when the following is observed:
The material strength at the mounting cutout is at least 2 mm.
The deviation of the evenness of the mounting cutout with an HMI device installed is
≤ 0.5 mm relative to the outside dimensions of the HMI device.
Degree of protection IP65
The IP65 degree of protection is only provided for a clamp mounting together with a ring
seal.
Degree of protection IP54
This degree of protection is provided for screw mounting.
Summary of Contents for SIMOTION P320-3
Page 14: ...Safety notes 1 2 Recycling and disposal SIMOTION P320 3 and Panel Fronts 14 Manual 02 2012 ...
Page 32: ...Description 2 4 SIMOTION panel fronts SIMOTION P320 3 and Panel Fronts 32 Manual 02 2012 ...
Page 100: ...Connecting 6 7 PROFINET strain relief SIMOTION P320 3 and Panel Fronts 100 Manual 02 2012 ...
Page 140: ...Standards and approvals A 3 Certificates SIMOTION P320 3 and Panel Fronts 140 Manual 02 2012 ...