If the motor has been ordered with brought-out leads, in this case you must comply with the
relevant conditions for Zone 2. It is assumed that the buyer, the installer and users of the
installation are familiar with these conditions and will carefully observe them.
6.5
Connecting the machine
6.5.1
Selecting cables
Take the following criteria into account when selecting the connecting cables:
● Rated current
● Rated voltage
● Possibly a service factor
● System-dependent conditions, such as ambient temperature, routing type, cable cross-
section as defined by required length of cable, etc.
● Requirements according to IEC/EN 60204‑1
● Dimensioning for bundled cable routing, e.g. according to DIN VDE 0298 Part 4 or
IEC 60364-5-52
● Requirements according to IEC/EN 60079-14
● Configuration notes
● Observe the information in EN / IEC 60034-1 (VDE 0530-1) regarding operation at the limits
of A and B zones, especially in respect of temperature increase and deviation of the
operating data from the rated data stamped on the rating plate. It is not permissible that
these limits are violated.
● Connect up so that a permanently safe electrical connection is guaranteed (no protruding
wire ends); use the assigned cable-end fittings (e.g. cable lugs, end sleeves).
Connect up the line supply voltage and arranged the disconnecting link in accordance with
the circuit diagram provided in the terminal box.
● Select the connecting cables in accordance with DIN VDE 0100 taking into account the
rated current and the installation-specific conditions – e.g. ambient temperature, routing
method etc. - according to DIN VDE 0298 and/or EN / IEC 60204‑1.
The technical specifications stipulate the following that have to be taken into account with
respect to the motor connection:
● Direction of rotation
● The number and arrangement of the terminal boxes.
● The circuit and connection of the motor winding
Electrical connection
6.5 Connecting the machine
1MB5 SH 400/450
70
Operating Instructions, 05/2019, A5E45959221A
Summary of Contents for SIMOTICS XP 1MB5 SH400
Page 2: ......
Page 10: ...Table of contents 1MB5 SH 400 450 8 Operating Instructions 05 2019 A5E45959221A ...
Page 156: ...Service support 1MB5 SH 400 450 154 Operating Instructions 05 2019 A5E45959221A ...
Page 160: ...Quality documents 1MB5 SH 400 450 158 Operating Instructions 05 2019 A5E45959221A ...
Page 165: ......