7.10
Set values for temperature monitoring (slot thermometer)
Before the machine runs for the first time, set the alarm and shutdown temperatures at the
temperature monitoring.
1. Measure the normal operating temperature T
op
at the installation location in ° C.
2. Set the values for shutdown and warning corresponding to the operating temperature T
op
.
Table 7-2
Alarm and shutdown temperatures of the temperature monitoring
Set value
Temperature
Prior to commissioning
Shutdown
145 °C
In operation
Alarm
T
op
+ 10 K ≤ 165 °C
Shutdown
T
op
+ 15 K ≤ 180 °C
7.11
Switching off the machine
● Do not switch off the water-cooling system immediately after switching off the machine.
Wait for the machine to cool. This will prevent the accumulation of residual heat.
Start-up
7.10 Set values for temperature monitoring (slot thermometer)
SIMOTICS T-1FW4 Heavy Duty 1FW4407-1KM81-1BC0-Z
72
Operating Instructions 11/2018