Connecting
6.2 Electrical connection
1FE1 synchronous built-in motors
108
Hardware Installation Manual, 12/2016, 610.43000.40b
6.2.7
Connecting to a converter
To connect the motor to a converter, use MOTION-CONNECT cables or shielded connecting
cables.
The braided shielding must have good electrical conductivity. Prefer braided shielding made
of copper or aluminum.
The shield must be connected at both ends to the motor and the converter; unshielded cable
ends must be kept as short as possible.
Attach the shielding with a large area as 360° contact to the converter and to the motor. Use
for instance, EMC glands at the cable entries.
6.2.8
Connection overview
The circuit diagram contains information about wiring and connecting the motor winding.
1
Ground connection
2
Temperature sensor (1 x reserve)
3
Encoders
4
VP module (if required)
Figure 6-2
Circuit diagram with SIMODRIVE (example)