● Appropriately configured control and speed monitoring functions ensure that the motor
cannot exceed the permissible speeds specified in the technical data. See also the system-
specific documentation.
● The minimum insulation resistance values are within tolerance.
● Minimum air clearances have been maintained.
● Any supplementary motor monitoring devices and equipment have been correctly
connected and are fully functional.
● The values for "Warning" and "Shutdown" are set at the monitoring devices.
● All brakes and backstops are operating correctly.
See also
Technical data and drawings (Page 101)
Switching overvoltages
When high-voltage machines with starting current I
A
≤ 600 A are switched off while starting or
after they have been blocked, then in individual cases inadmissibly high switching overvoltages
for the stator winding insulation can occur through multiple restrikes.
The peak voltages which arise as a result can damage the winding insulation.
● If you are using vacuum circuit breakers and vacuum contactors, use an appropriate surge
suppressor, such as the Siemens 3EF (zinc oxide varistor with spark gap).
● An additional RC arrester (resistor and capacitor connected in series) makes sense at
unfavorable operating points/under unfavorable line supply conditions.
See also
Switching high-voltage motors (Page 24)
Cooling
● Check that the machine cooling is available for commissioning.
Cooling water supply
● The cooling water supply is connected and ready for operation.
● The cooling water supply is switched on. The data can be found on the rating plate.
● Cooling water is available in the configured quality and quantity.
● Vent the cooling ducts when filling. Completely fill the cooling ducts with water.
Adequate machine cooling cannot be guaranteed if the cooling ducts are not completely
filled with water. The machine can overheat.
● Ensure that the DE drain plug on the lower side is tightly screwed in.
● Then fill the cooling circuit.
Commissioning
7.1 Prior to commissioning
SIMOTICS HV C 1NA14544WA600AG0-Z
60
Operating Instructions 06/2018
Summary of Contents for Simotics HV C 1NA14544WA600AG0-Z
Page 2: ...14 06 2018 09 34 V3 00 ...
Page 10: ...Table of contents SIMOTICS HV C 1NA14544WA600AG0 Z 10 Operating Instructions 06 2018 ...
Page 74: ...Operation 8 9 Faults SIMOTICS HV C 1NA14544WA600AG0 Z 74 Operating Instructions 06 2018 ...
Page 100: ...Service and Support SIMOTICS HV C 1NA14544WA600AG0 Z 100 Operating Instructions 06 2018 ...
Page 104: ...Quality documents SIMOTICS HV C 1NA14544WA600AG0 Z 104 Operating Instructions 06 2018 ...
Page 106: ...Additional documents SIMOTICS HV C 1NA14544WA600AG0 Z 106 Operating Instructions 06 2018 ...
Page 110: ...Index SIMOTICS HV C 1NA14544WA600AG0 Z 110 Operating Instructions 06 2018 ...
Page 111: ......