6.6.7
Terminating the connection work (auxiliary circuit)
1. Before closing the auxiliary terminal box, please check that:
– The cables are connected in accordance with the terminal diagram.
– The cables are freely arranged so that they cannot come into contact with the machine,
and the cable insulation cannot be damaged.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– The cable glands are firmly tightened, are suitable with respect to the degree of
protection, type of cable routing, permissible cable diameter, etc., and have been
mounted in full compliance with specifications and regulations
– The threads in the connection plate are sealed using cable and conductor entries, thread
adapters or sealing plugs that achieve the respective degree of protection.
– Unused cable entries are sealed. The sealing elements are firmly screwed in, and can
only be released using a tool.
– All of the seals/gaskets and sealing surfaces of the terminal box are in good condition
– The screws of all of the screw clamps are fully tightened, even if they are not being used.
2. Close the auxiliary terminal box using the cover supplied for this purpose. See section
"Tightening torques for screw and bolt connections (Page 173)" for the tightening torque of
the fixing bolts for the cover.
Electrical connection
6.6 Connecting the auxiliary circuits
SIMOTICS FD 1MQ1
92
Operating Instructions 01/2019
Summary of Contents for SIMOTICS FD 1MQ1
Page 2: ...28 01 2019 14 14 V11 01 ...
Page 144: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MQ1 144 Operating Instructions 01 2019 ...
Page 170: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MQ1 170 Operating Instructions 01 2019 ...
Page 172: ...Service and Support SIMOTICS FD 1MQ1 172 Operating Instructions 01 2019 ...
Page 176: ...Quality documents SIMOTICS FD 1MQ1 176 Operating Instructions 01 2019 ...
Page 181: ......