
See also
Service and Support (Page 163)
4.19.5
Converter operation on a grounded network
NOTICE
Damage resulting from protective conductor currents
When the machine is operated with a converter with current limiting, but without ground-fault
monitoring, protective conductor currents of up to 1.7 times the phase conductor current can
flow if there is a ground fault on the output side. Neither the PE conductors of normally rated
multi-conductor connecting cables nor the PE connecting points of standard terminal boxes is
suitable for this purpose. Material damage can result.
● Use an appropriately sized PE conductor.
● Connect the PE conductor to the grounding terminal on the motor enclosure.
Preparations for use
4.19 Converter operation
SIMOTICS FD 1LH1
52
Operating Instructions 01/2019
Summary of Contents for SIMOTICS FD 1LH1
Page 2: ...23 01 2019 19 26 V11 01 ...
Page 28: ...Description SIMOTICS FD 1LH1 28 Operating Instructions 01 2019 ...
Page 122: ...Operation 8 10 faults SIMOTICS FD 1LH1 122 Operating Instructions 01 2019 ...
Page 140: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1LH1 140 Operating Instructions 01 2019 ...
Page 162: ...Disposal 11 5 Disposal of components SIMOTICS FD 1LH1 162 Operating Instructions 01 2019 ...
Page 164: ...Service and Support SIMOTICS FD 1LH1 164 Operating Instructions 01 2019 ...
Page 168: ...Quality documents SIMOTICS FD 1LH1 168 Operating Instructions 01 2019 ...
Page 173: ......