Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
79
Minimum pause time
A pause time is transferred with the "Start_Pause" command. SIMOCODE pro V PN (GP)
executes this command if the pause time is greater than the minimum pause time configured
in the device. The minimum pause time of the motor is configured with the SIMOCODE ES
software under "PROFIenergy." The minimum pause time is preset to the smallest possible
value 0.1 s. You can increase the minimum pause time if executing the command in longer
pauses is convenient for technological reasons.
End_Pause
The "End_Pause" command results in the stop command being canceled at the PLC/PCS
control station and the motor being switched on again via enabled control stations.
Note
Command "End_Pause"
The command to switch on has to be output again because subsequent automatic switch-on
is not performed.
Note
Switching on the motor in the paused condition
If the PLC/PCS control station is disabled, the motor can also be switched on in the paused
condition.
Query_Measurement
Depending on the use of the current measuring or the current-voltage measuring module,
the following measured values are supported:
Table 2- 29 Query_Measurement
Measurement-ID
PROFIenergy identifier
SIMOCODE pro identifier
Unit
4
Voltage (a-b)
Voltage U_L12 V
V
5
Voltage (b-c)
Voltage U_L31 V
V
6
Voltage (c-a)
Voltage U_L31 V
V
7
Current (a)
Phase current I_L1 A
A
8
Current (b)
Phase current I_L2 A
A
9
Current (c)
Phase current I_L3 A
A
33
Current average (abc)
Average phase current I_L A
A
34
Active power (total)
Active power P
W
36
Apparent power (total)
Apparent power S
VA
37
Power factor (total)
Cos phi
-
200
Active energy import (total) Energy W
Wh