Technical data
15.11 Typical reaction times
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
365
15.11
Typical reaction times
15.11.1
Typical reaction times of the SIMOCODE pro C/V device series
Table 15- 1 Typical reaction times of SIMOCODE pro C device series
Component
Time inputs
Time processing
Time outputs
Basic unit:
Thermistor:
PROFIBUS:
Set delay time
400 ms
30 ms
30 ms
10 ms
-
30 ms
Current measurement:
Internal ground fault:
200 ms
300 ms ... 600 ms + set delay
-
-
Table 15- 2 Typical reaction times of SIMOCODE pro V device series
1)
Component
Time: Inputs
Time: Processing Time:
Outputs
Basic unit:
Thermistor:
PROFIBUS, PROFINET:
Set delay time
400 ms
5 ms
5 ms
10 ms
-
5 ms
when using UM
when using UM+
2), 4)
Current measurement:
Voltage measurement:
Active power / cos phi:
Internal ground fault:
300 ms
300 ms
1000 ms
300 ms ... 600 ms
3)
200 ms
200 ms
200 ms
200 ms ... 600 ms
3)
-
-
-
-
Ground-fault module / external
ground fault
100 ms
3)
-
Digital modules:
•
24 V DC version
•
110 V - 240 V AC/DC version
15 ms + delay time
50 ms + delay time
25 ms
25 ms
Analog module
150 ms
25 ms
Temperature module
500 ms
-
DM-F Local
≤
75 ms + delay time
30 ms
DM-F PROFIsafe
15 ms + delay time
30 ms
1) Based upon a typical hardware set-up: Basic unit + current measuring
2 expansion modules
Reaction time = inputs conversion time + internal processing time + outputs conversion time
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...