Technical data
15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units
SIMOCODE pro
338
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units
PROFINET IO system redundancy
Yes
PROFIenergy measured values
Yes
PROFIenergy shutdown
Yes
Rated control supply voltage Us (according to
DIN EN 61131-2)
Warning
For the 24 V DC power supply, always use an
SELV or PELV power supply unit!
110 V to 240 V AC/DC, 50/60 Hz
24 V DC
Operating range
0.85 x Us to 1.1 x Us (startup)
0.85 x Us to 1.1 x Us (operation)
0.85 x Us to 1.2 x Us (startup)
0.80 x Us to 1.2 x Us (operation)
Power consumption
SIMOCODE pro V PN (3UF7011) and
SIMOCODE pro V EIP (3UF7013):
Measurement conditions: Room temperature,
combination of basic unit, current/voltage
acquisition module and operator panel with
display, each with 2 LEDs switched on and
active inputs and outputs, active thermistor, and
100 MBd bus transmission rate
SIMOCODE pro V PN basic unit:
8.3 VA / 4.8 W
3.9 W
SIMOCODE pro V EIP basic unit:
8.3 VA / 4.8 W
3.9 W
Rated insulation voltage U
i
300 V (at pollution degree 3)
Rated impulse withstand voltage U
imp
4 kV
Power failure backup time (longer power
failures lead to shutdown of the relay outputs
(monostable))
•
24 V DC
•
110 V to 240 V AC/DC
Typ. 20 ms
Relay outputs
Number
3 monostable relay outputs
Function
Isolated NO contacts (NO contact response parameterizable via internal
signal conditioning), 2 relay outputs connected to common potential, one
separate relay output, freely-assignable to control functions (e.g. line,
star or delta contactor or operating state status information.)
Stipulated short-circuit protection for auxiliary
contacts (relay outputs)
•
6 A fuse inserts, operational class gG; 10 A quick-response
(IEC 60947-5-1)
•
Miniature circuit breaker 1.6 A, C characteristic (IEC 60947-5-1)
•
Miniature circuit breaker 6 A, C characteristic (Ik < 500 A)
Rated uninterrupted current
•
5 A
•
6 A at max. +50 °C
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...