![Siemens SIMOCODE pro C System Manual Download Page 297](http://html.mh-extra.com/html/siemens/simocode-pro-c/simocode-pro-c_system-manual_1265400297.webp)
Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
297
Event
(alphabetical)
Description
Troubleshooting
Acknowledgment /
fault rectification
Contactor
control
Error
No.
1)
Wrong
password
SIMOCODE pro parameters are
protected by a password. An
attempt has been made to
change the parameters without
entering the password.
Please use the correct
password for changing the
parameters. If you do not
know the password, new
parameters can only be
entered after the factory
settings have been
restored. For a description
of how to restore the
factory settings, see
Chapter Restoring factory
Phase
unbalance
The limit value for phase
unbalance has been exceeded.
Phase unbalance can cause an
overload. Possible causes:
•
Phase failure
•
Fault in the motor windings.
Check the motor feeder
and the motor.
Reset
Tripped
25
Feedback
(FB) OFF
The current flow in the motor
feeder has been interrupted
without the motor feeder being
turned off.
•
The main circuit has
been interrupted (fuse,
circuit breaker, main
switch).
•
The motor contactor or
contactor control is
defective
Reset
Tripped
11
Feedback
(FB) ON
Current is flowing in the motor
feeder without the motor feeder
being switched on
•
Contactor contacts
have been manually
activated
•
Contactor has not
been switched on via
SIMOCODE
Clear the fault;
reset
Tripped
10
Test Position
Feedback
(TPF)
Current is flowing in the motor
feeder although the motor feeder
is in the test position (TPF).
The main circuit is not
interrupted in test
operation.
Reset
Tripped
17
Memory
module read
in
The parameters of the memory
module were read into
SIMOCODE.
Memory
module
cleared
The memory module was cleared
and is now back in as-delivered
state.
Memory
module
programmed
The reparameterization was
accepted in the memory module.
Memory
module write-
protected
The memory module is
completely write-protected.
Deactivate write protection
of the memory module.
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...