Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
294
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Event
(alphabetical)
Description
Troubleshooting
Acknowledgment /
fault rectification
Contactor
control
Error
No.
1)
DM-FL
configuration
mode
The DM-F Local is in
"configuration mode"; the
"DEVICE" LED on the front of the
DM-F Local is illuminated yellow.
Complete the
configuration (see manual
"Fail-safe Digital Modules
SIMOCODE pro Safety",
Chapter 7.4)
3)
.
DM-FL cross
circuit
Cross circuit in sensor circuit of
DM-F Local; the "SF" (general
fault) LED on the front of the
DM-F Local is illuminated red.
•
Check the wiring of
both sensor circuits for
cross circuiting
•
Rectify the fault.
Reset
Tripped
68
DM-FL
waiting for
start-up test
The DM-F LOCAL is in the
"Waiting for start-up test" status.
Perform the startup test by
actuating the sensor in the
sensor circuit.
DM-FP Prm
error
The parameter settings of the
PROFIsafe profile are incorrect
or the set PROFIsafe address is
not identical to the configured
address.
Check the
communication /
PROFIsafe parameters of
SIMOCODE pro that were
set on the IO controller.
Double 0
Both torque switches have
activated simultaneously. The
motor feeder has been turned off.
•
Open circuit torque
switch.
•
Torque switch is
defective.
Tripped
13
Double 1
Both limit switches have
activated simultaneously.
Limit switch defective
Tripped
14
End position Except positioner 5 control
function: The state of the limit
switches has changed without a
command (positioner has left the
end position without a
command).
Counter command
"OPEN /
CLOSED!"
Tripped
15
External
ground fault
External ground-fault monitoring
has responded. An impermissibly
high residual current is flowing.
Please check the motor
connection cable for
damage.
Reset
Tripped
29
External
fault 1, 2, 3,
4, 5 or 6
A signal is pending at the input
(socket) of the "External fault 1,
2, 3, 4, 5 or 6" standard function.
Check the motor feeder.
Tripped
56,
57,
58,
59,
60,
61
Required
function is
not supported
At least one parameterized
function is not supported by the
version of the basic unit.
Activate only the functions
that are supported by the
version of the basic unit.
Hardware
fault
The SIMOCODE pro basic unit
hardware is defective.
Replace the basic unit.
See Chapter Replacing
components (Page 279).
Clear the fault.
Tripped
0
Initialization
module write-
protected
The initialization module is
completely write-protected.
Deactivate write protection
of the initialization module
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...