![Siemens SIMOCODE pro C System Manual Download Page 290](http://html.mh-extra.com/html/siemens/simocode-pro-c/simocode-pro-c_system-manual_1265400290.webp)
Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
290
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Example:
The most recent "power-on" event was logged at a device operating time of 17 days,
21 hours and 31 minutes. Therefore, at the moment of "Power - On", the device was
operating (supplied with voltage) for 17d 21h 31min. The "Number of starts >" fault was
logged at a device operating time of 18 days, 22 hours, 17 minutes, i.e. 24h 46min after the
most recent "Power - On."
When using a DM-F, the events "Enabling circuit closed" and "Enabling circuit open" are
logged for the DM-F Local and/or the DM-F PROFIsafe in a separate window:
●
Time
●
Event: "Enabling circuit closed" or "Enabling circuit open"
–
Number:
Line 1 200 or 202
Line 2 201 or 203
–
Text:
Line 1 "DM-F Local enabling circuit 0 -> 1" or
"DM-F PROFIsafe enabling circuit 0 -> 1"
Line 2 "DM-F Local enabling circuit 1 -> 0" or
"DM-F PROFIsafe enabling circuit 1 -> 0."
The current DIP switch position of the "DM-F Local" and/or the "DM-F PROFIsafe" is
displayed under "DIP switch position DM-F during the last event".
See also Chapter "Data record 72 - Error buffer" in the manual SIMOCODE pro -
Communication (
https://support.industry.siemens.com/cs/ww/en/view/109743960
13.4.2
Event memory
In addition to the error buffer, various events can be stored in the event buffer
Note
This event memory is supported by the SIMOCODE pro V basic unit as from firmware
version V3.0.
The following events are stored:
•
last event "DM-F enabling circuit closed"
•
last event "DM-F enabling circuit open"
•
Initialization module read in
•
Initialization module written.
See also Chapter "Data record 73 - Event buffer" in the manual SIMOCODE pro -
Communication (
https://support.industry.siemens.com/cs/ww/en/view/109743960
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...