7.2 Fault Recorders
75
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
7.2.1.2.7
Network Trigger
If several SIMEAS R-PMU are combined to form a local network (LAN), the triggered device can
use the network to send UDP broadcast telegrams to the other SIMEAS R-PMU devices and
start a TAR fault recording there. The subnet is defined via
IP Address SIMEAS R-PMU
and
Subnet Mask SIMEAS R-PMU
, see chapter 12.7.2 and chapter 10.2.2.
You can set separately, whether the SIMEAS R-PMU is to send network trigger signals or to
evaluate incoming network trigger requests. If incoming network trigger requests are evaluated,
only the TAR is able to start a retrigger. Retriggering is not possible via a new network trigger. If
SIMEAS R-PMU receives a network trigger, the trigger time stamp indicates the receipt time of
the network trigger.
If SIMEAS R V2/3 devices are also used in the same network, the SIMEAS R-PMU can evaluate
a network trigger received from these devices and start its own record. The opposite case, i. e.,
that the SIMEAS R V2/3 device starts a fault record upon receipt of a trigger from a SIMEAS R-
PMU device, is only possible if both devices refer to the same time base.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...