7
7.1 Phasor Measurement Unit (PMU)
63
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Measures to reduce the data rate.
−
Decreasing the reporting rate
−
Transfer of 16 bit integer data instead of 32 bit floating point data
−
Transfer of positive sequence system data instead of phasors
−
Deactivating one DAU for PMU measurements
Table 7-8
Serial or modem transmission:
Data transfer rate depending on the configuration and reporting rate in kbit/s,
data format 16 bit integer
Configuration
Type
Reporting rate (Hz)
10
12
15
20
25
30
50
60
1 AC DAU
Positive-sequence system
3
4
5
6
8
9
15
18
1 AC DAU
Phasors
5
6
7
10
12
15
25
30
2 AC DAUs
Positive-sequence system
4
5
6
9
11
13
21
26
2 AC DAUs
Phasors
8
10
12
16
20
24
40
48
4 AC DAUs
Positive-sequence system
7
8
10
14
17
20
34
41
4 AC DAUs
Phasors
14
17
21
29
36
43
71
86
1 DDAU
Process values
4
4
6
7
9
11
18
22
2 DDAUs
Process values
6
7
8
11
14
17
28
33
1 BDAU
Binary values
3
3
4
5
6
8
13
15
2 AC DAUs
2 DDAUs
Positive-sequence system/
process values
9
11
14
19
23
28
46
56
2 AC-DAUs
1 DDAU
1 BDAU
Phasors /
process values /
binary values
11
13
16
21
27
32
54
64
Note
The 32 bit floating point data format is not supported for the PMU data communication via
RS232.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...