16.1 Technical Data of the SIMEAS R-PMU
245
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1.4 Analog and Binary Inputs and Outputs
Slot 2
(ZE 8/16, one DAU)
Can be equipped as per Table 16-2
Slots 2 to 5
(ZE 32/64, up to four DAUs)
Can be equipped as per Table 16-2
Measured value processing
A/D converter: 16 bit, 64 times oversampling, 92 dB dynamic range
Table 16-2
Configuration options
VCDAU
8 analog (4 current/4 voltage) and 16 binary
channels
VDAU
8 analog (8 voltage) and 16 binary channels
CDAU
8 analog (8 current) and 16 binary channels
DDAU
8 analog (8 current DC ±20 mA or
8 voltage DC ±1 V or DC ±10 V)
and 16 binary channels
BDAU
32 binary channels
Table 16-3
VCDAU, VDAU and CDAU
Nominal
frequency
Sampling
frequency
Frequency range
Samples/cycle
50 Hz
9,600 Hz
25 Hz to 60 Hz
192
60 Hz
11,520 Hz
30 Hz to 70 Hz
192
Table 16-4
DDAU
Nominal
frequency
Sampling
frequency
Frequency range
Samples/cycle
50 Hz
9,600 Hz
0 Hz to 500 Hz
192
60 Hz
11,520 Hz
0 Hz to 500 Hz
192
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...