14
14.3 Extending the Existing Hardware
203
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
17. Plug the connecting line (ribbon cable) between the front plate and the CPU module into the
CPU module.
18. Screw the front plate back to the device. Be careful not to pinch the ribbon cable when
mounting the front plate.
19. Screw the knurled nut to switch S1.
20. Screw the cover back into place.
21. Connect the measuring signals to the new adapters.
22. Apply the supply voltage to the device.
23. Switch the device on using switch S1.
24. Connect a notebook to the service interface COM S at the front of the device.
25. Enable the new module using the OSCOP P system program and set the parameters for the
individual channels. For detailed information regarding the parameterization, please refer to
Chapter 12.
14.3.3
Extending a SIMEAS R-PMU by Communication Components
Communication components are analog or ISDN modems or X.25-PAD modules. They are
connected to the COM 1 interface at the rear panel of the SIMEAS R-PMU.
1. Switch the SIMEAS R-PMU off using switch S1.
2. Connect the data end device to the COM 1 interface at the rear panel of the SIMEAS R-PMU
using the appropriate cable.
3. Build up a connection between the data end device and the telephone socket.
4. Switch the data end device on.
5. Switch the SIMEAS R-PMU on using switch S1.
6. Connect a notebook to the service interface COM S at the front side of the SIMEAS R-PMU.
7. Enable the new modem using the OSCOP P system program and set the connection
parameters. For detailed information regarding the parameterization, please refer to
Chapter 12.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...