12.13 Transient Phasor Recorder (TPR)
168
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12.13
Transient Phasor Recorder (TPR)
12.13.1 Time Settings
First of all, select the dialog
Transient Phasor Recorder
to set the run time parameters for
the device.
Figure 12-32 TPR, Time Settings tab
Select the dimension of the run times to be set from the drop-down menu of the
Timebase
box. For reasons of clarity, all times are displayed in the same dimension. When the unit of
time is changed, all times will be readjusted.
Enter in the
Recording Rate
box
an integer between 1 and 5 for the recording rate in nominal
cycles.
Enter the recording time of the events preceding the fault in the
Prefault Time
box.
Define the length of a record starting from the trigger time in the
Recording Time
box.
Enter the recording time for a manual trigger in the
Recording time for manual trigger
box.
Enter the blocking time for manual channels in the
Retrigger blocking time for analog
inputs
box. During this period, no other trigger condition is recognized for this channel.
Enter the blocking time for binary inputs in the
Retrigger blocking time for binary inputs
box. During this period, no other trigger condition is recognized for this channel.
Note
A time must be entered in every input field.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...