Fail-Safe Electronic Modules
8.1 8 /16 F-DI DC24V PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
59
8.1.4
Parameters for the 8/16 F-DI DC24V PROFIsafe Electronic Module
Parameters in
STEP 7
The following table presents the parameters that can be assigned to the 8/16 F-DI DC24V
PROFIsafe electronic module.
Table 8-2
Parameters for the 8/16 F-DI DC24V PROFIsafe Electronic Module
Parameters
Range
Default
Type of
parameter
Range of
effectiven
ess
F-parameters:
F_destination_addre
ss
1 to 1022
Assigned by
STEP 7
Static
Module
F-monitoring time
10 to 10000 ms
150 ms
Static
Module
Module Parameters:
Input delay
0.5; 3; 15 ms
3 ms
Static
Module
Short-circuit test
Cyclic/Disable
Cyclic
Static
Module
Behavior after
channel faults*
Passivate the entire
module/Passivate the
channel
Passivate the entire
module
Static
Module
Channel n, n+4
Enabled/disabled
Enabled
Static
Channel
group
Evaluation of the
sensors
1oo2 evaluation/
1oo1 evaluation
1oo2 evaluation
Static
Channel
group
Type of sensor
interconnection
1-channel;
2-channel equivalent;
2-channel nonequivalent
2-channel equivalent
Static
Channel
group
Behavior at
discrepancy
Provide last valid value;
Provide value 0
Provide last valid value Static
Channel
group
Discrepancy time
10 to 30000 ms
10 ms
Static
Channel
group
Reintegration after
discrepancy error
Test of 0-signal not
required/Test of 0-signal
required
Test of 0-signal not
required
Static
Channel
group
* This setting is only relevant when the S7 Distributed Safety V 5.4 or higher optional package is
installed.