Commissioning the device
4.4 Configuring the device
Comfort Panels
Operating Instructions, 03/2012, A5E03404994-02
121
5.
If you have selected manual address assignment, enter the corresponding addresses
under "IP Address", "Subnet Mask" and if necessary under "Default Gateway".
NOTICE
PROFINET I/O error if the PN_X1 and PN_X3 subnet masks are identical
In principle, the two network adapters may be assigned to a shared physical
subnetwork.
If you have enabled PROFINET services for PN_X1 and the IP subnet masks of the two
network adapters are identical, PROFINET I/O errors may occur.
Assign a different entry for each network adapter in PROFINET I/O operation under
"Subnet Mask".
Note
Alternatively, you can configure the network address in the "Devices & Networks" editor in
WinCC. You can find more information on this topic in the online help of WinCC.
6.
If a name server is used in the network, change to the "Name Servers" tab.
7.
Enter the appropriate addresses.