Communication modules
6.3 GDM memory module CP52M0
SIMATIC TDC hardware
System Manual, 08/2017, A5E01114865-AL
139
6.3.3
Status and fault displays
Status displays for CP52M0
Table 6- 10 LED status displays for the CP52M0 GDM memory module
LED display
Status of the CP52M0 module
H1
H2
Off
Off
During voltage run-up
Off
On
All FPGAs in the GDM rack (CP52M0 and CP52IO) are parameter-
ized; the module is initialized
On
Off
The module i initialized and operates without errors
On
On
After 3.3 V or 2.5 V voltage failure
•
Hardware failure => Switch off the rack and replace CP52M0
Status displays at the digital outputs
Table 6- 11 Status displays at the digital outputs of CP52M0
Digital output
Display/status
DA01 to 11
Indicate the CP52IO slot (slots 2-12) from which the operating state of the
four fiber-optic interfaces is displayed on DA12-DA15. The operating state
display of the individual CP52IO modules is cycled at seconds intervals.
DA12 to 15
Indicate the operating state of the four fiber-optic interfaces of a CP52IO
(DA12 fiber-optic interface 1, DA13 fiber-optic interface 2, etc.).
•
Logical status "1" => FOC interface is OK
•
Logical status "0" => Error at FOC interface, or CP52IO is missing
DA16
•
Logical status "1" => RUN operating state
•
Logical status "0" => STOP operating state