Assigning Parameters to and Calling the S7-Graph FB
S7-GRAPH for S7 300/400 Programming Sequential Control Systems
9-8
C79000-G7076-C526-01
9.6
Output Parameters of the S7-Graph FB
Parameter
Data
Type
Description
Min.
Std.
Max.
User-
def.
ENO
BOOL
Enable output. When the FB is active and
no error has occurred, ENO has the value
1, otherwise 0
á
á
á
á
S_NO
INT
STEP
_NUMBER:
Display step number
á
á
á
S_MORE
BOOL
MORE_
STEP
S:
Other steps are active
á
á
á
S_ACTIVE
BOOL
STEP
_ACTIVE:
Displayed step is active
á
á
á
S_TIME
TIME
STEP
_TIME:
Step activation time
á
S_TIMEOK
TIME
STEP
_TIME_OK:
No error in step activation time
á
S_CRITLOC
DWORD
STEP
_CRITERIA_INTERLOCK:
Interlock criteria bits
á
S_CRITLOC
ERR
DWORD
S_CRITERIA_IL_LAST_ERROR:
Interlock criteria bits for event L1
á
S_CRITSUP
DWORD
STEP
_CRITERIA_SUPERVISION:
Supervision criteria bits
á
S_STATE
WORD
STEP
_STATE:
Step state bits
á
T_NO
INT
TRANSITION_NUMBER:
Valid transition number
á
T_MORE
BOOL
MORE_TRANSITIONS:
Other valid transitions available for display
á
T_CRIT
DWORD
TRANSITION_CRITERIA:
Transition criteria bits
á
T_CRITOLD
DWORD
T_CRITERIA_LAST_CYCLE:
Transition criteria bits from last cycle
á
T_CRITFLT
DWORD
T_CRITERIA_LAST_FAULT:
Transition criteria bits for event V1
á
ERROR
BOOL
INTERLOCK_ERROR:
Interlock error (any step)
á
FAULT
BOOL
SUPERVISION_FAULT:
Supervision error (any step)
á
ERR_FLT
BOOL
IL_ERROR_OR_SV_FAULT:
Group disturbance
á
á
á
SQ_ISOFF
BOOL
SEQUENCE_IS_OFF:
Sequencer idle (no step active)
á