Safety Mechanisms
Fail-Safe Systems
A5E00085588-03
3-7
3.7
Fail-Safe User Times
Time values generated in the Safety Program with the F_TP, F_TON and F_TOFF
blocks are monitored by means of safety mechanisms of the CPU. To do this, two
mutually independent time counters are compared. As long as the discrepancy
between the two counters is less than 10 ms within a time period of 50 s, the time
is considered correct. If the discrepancy is larger, a hardware fault is assumed and
the Safety Program is disabled.
The maximum inaccuracy of user times can be calculated on the basis of the
following table:
User Times From
To
Max. Inaccuracy
10 ms
50 s
± 5 ms
> 50 s
100 s
± 10 ms
...
...
...
> n* 50 s
(n+1)*50 s
± (n+1)*5 ms
The actual inaccuracy is considerably less than this. Also note the time inaccuracy
that occurs due to processing in the cyclic interrupt scan cycle.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...