B.5
Diagnostic data of the analog input modules as of byte 2
Overview
The structure and contents of the different bytes of the diagnostic data for the special analog
input modules are described below. General rule: When an error occurs, the bit concerned is
set to "1".
You will find a description of possible error causes and appropriate remedies in the section on
the special module.
Bytes 2 and 3 of the SM 431; AI 16 x 16 bit
Table B-18
Bytes 2 and 3 of the diagnostic data of the SM 431; AI 16 x 16 bit
Byte
Bit
Meaning
Byte 2
7
0
6
0
5
0
4
0
3
0
2
Operating mode 0: RUN; 1: STOP
1
0
0
Measuring range module incorrect or missing
Byte 3
7
0
6
Hardware interrupt lost
5
0
4
ADC/DAC error
3
RAM error
2
EPROM error
1
0
0
0
Diagnostic data of signal modules
B.5 Diagnostic data of the analog input modules as of byte 2
S7-400 Automation System Module Data
420
Reference Manual, Ausgabe 11/2016, A5E00850736-08